FieldServer FS-8700-83 Configuring the FieldServer as a Gamewell Serial Driver Client

Models: FS-8700-83

1 24
Download 24 pages 19.21 Kb
Page 5
Image 5
4.Configuring the FieldServer as a Gamewell Serial Driver Client

FS-8700-83 Gamewell

Page 3 of 24

4.Configuring the FieldServer as a Gamewell Serial Driver Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver diskette).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Gamewell Serial Driver Server

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Gamewell Serial Driver communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

4.1Data Arrays

 

 

Section Title

 

 

 

 

 

Data_Arrays

 

 

 

 

 

 

Column Title

 

Function

 

Legal Values

 

Data_Array_Name

Provide name for Data Array

 

Up to 15 alphanumeric

 

 

 

 

 

 

characters

 

Data_Format

Provide data format. Each data array can

FLOAT, BIT, UInt16, SInt16,

 

 

 

only take on one format.

 

Packed_Bit, Byte,

 

 

 

 

 

 

Packed_Byte,

 

 

 

 

 

 

Swapped_Byte

 

Data_Array_Length

Number of Data Objects. Must be larger

1-10,000

 

 

 

than the data storage area required for

 

 

 

 

the data being placed in this array.

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

//

Data Arrays

 

 

 

 

 

//

 

 

 

 

 

 

Data_Arrays

Data_Format,

Data_Array_Length

 

Data_Array_Name,

 

DA_AI_01,

UInt16,

 

200

 

 

DA_AO_01,

UInt16,

 

200

 

 

DA_DI_01,

Bit,

 

200

 

 

DA_DO_01,

Bit,

 

200

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 5
Image 5
FieldServer FS-8700-83 instruction manual Configuring the FieldServer as a Gamewell Serial Driver Client, 4.1Data Arrays