FieldServer 4.3Client Side Nodes, FS-8700-83 GamewellPage 5 of, Section Title, Column Title

Models: FS-8700-83

1 24
Download 24 pages 19.21 Kb
Page 7
Image 7
FS-8700-83 GamewellPage 5 of 24

FS-8700-83 GamewellPage 5 of 24

4.3Client Side Nodes

Section Title

 

 

Nodes

 

 

Column Title

Function

Legal Values

Node_Name

Provide name for node

Up to 32 alphanumeric

 

 

characters

Node_ID

Gamewell panel node address.

0-256

 

The Node Id has no meaning

 

 

when the FieldServer is

 

 

connected directly to Gamewell

 

 

panel. When connecting to a

 

 

Gamewell panel directly always

 

 

set the Node_ID to zero. When

 

 

connecting to a Gamewell

 

 

SmartNet terminal. The

 

 

Node_ID is important and

 

 

should correspond to the

 

 

Node_ID’s of the panel’s

 

 

connected to the SmartNet

 

 

terminal.

 

 

 

 

Protocol

Specify protocol used

Gamewell

Port

Specify which port the device is

P1-P8, R1-R2

 

connected to the FieldServer.

 

 

The use of R1 and R2 is only

 

 

appropriate when a 232/485

 

 

converter is used. The

 

 

Gamewell panels only have a

 

 

232 port available for

 

 

connection.

 

Example

 

 

 

 

 

// Client Side Nodes

 

 

Nodes

Node_Name, Node_ID, Protocol, Port

Panel1 , 0 , Gamewell, P8

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 7
Image 7
FieldServer 4.3Client Side Nodes, FS-8700-83 GamewellPage 5 of, Section Title, Column Title, Function, Legal Values