FS-8700-83 GamewellPage 4 of 24
4.2Client Side Connections
Section Title |
|
|
Connections |
|
|
Column Title | Function | Legal Values |
Port | Specify which port the device is | |
| connected to the Bridge |
|
Baud | Specify baud rate | 2400 |
| The driver supports all standard |
|
| baud rates 110 – 115200. |
|
| Gamewell panels only support a |
|
| baud rate of 2400. |
|
Parity* | Specify parity | None |
| The driver supports the following |
|
| options. Even, Odd, None, Mark, |
|
| Space |
|
| The Gamewell panels only |
|
| support the use of no parity. |
|
Data_Bits* | Specify data bits | 8 |
Stop_Bits* | Specify stop bits | 1 |
Protocol | Specify protocol used | Gamewell |
|
|
|
Handshaking* | Specify hardware handshaking | None |
Poll _Delay* | Time between internal polls | |
|
| default 1 second |
IC_Timeout | This driver does not use an inter | 0 |
| character timeout system. Failing |
|
| to set the IC_Timeout to zero will |
|
| result in driver errors. |
|
Example |
|
|
//Client Side Connections
Connections
Port, Baud, Parity, Protocol, Handshaking, Poll_Delay, IC_Timeout
P8, 9600, None, Gamewell, None , 0.100s , 0
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408)