Based on the table below if a message contains the string ‘Fire Alarm in’ then the action number will be stored as 11.

Value Action

Description

255

Driver did not recognize action type

System Setup

 

1 Skip System I/O Assignments

System power up

2 Begin System I/O Assignments

System programming itself

3 Programming Mode Entered

Ignore any data from this point until "Exit Program

Mode" is received

4 Exit Program Mode

See Programming Mode Entered

Control

 

5 Commencing System Reset

System reset button has been depressed

6 System Idle

System reset completed system is normal

7 System Acknowledged

System Acknowledge button depressed

8 Signals Deactivated

System Signal Silence button depressed Audibles

Silencing

9 Signals Activated

System Signal Silence button depressed Audibles

reactivating

10 Signals Silenced Automatically

System automatically silenced the audible signals

Fire Alarm

 

11 Fire Alarm in

 

Supervisory

 

12 Supv. Event in

 

Generic

 

13 Genr. Event in

 

Security Alarm

 

14 Security Alarm in

 

Pre Alarm

 

15 Ver. Seq. in

Verification sequence started

16 Pos Al. Seq. in

Positive Alarm Sequence started

17 Pre-Alarm in

Pre alarm present

Fault

 

18 Alarm Tested in

Message during walk test

19 AtoD Malfunction

System Problem

20 LCD Malfunction

System Problem

22 System In Walk Test

Start partial or Full system walk test mode

23 System Out Of Walk Test

Finished system walk test mode

24 System l/Os By Passed

Bypass system circuits or devices

25 All By Passed I/Os Cleared

System not bypassed

26 I/0 Bypassed,

Starts ID of Circuit or point bypassed

27 Remote Annunciators Not Responding System Problem

28 Remote Annunciators OK

System Problem Restored

29 Key Stuck in

System Problem

30 Display Missing for

System Problem

31 Bad Card @

System Problem

32 Card Missing @

System Problem