4.4.7.Map Descriptor Example 4 - Analog Output 1 (Area Machine)
A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will command an area to a preset scene on the Lutron eLumen panel. Scenes range from 0 to 65535 and area numbers range from 0 to 511
BACNet IP Map Descriptor
// Client Side Map Descriptors
Map_Descriptors  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Map_Descriptor_Name,  | Data_Array_Name,  | Data_Array_Offset,  | Function,  | Node_name,  | Data_Type,  | Object_ID,  | Length,  | Relinquish_Default  | 
SMD000_AO,  | Analog_Output,  | 0,  | Server,  | Virtual_BCU_11,  | AO,  | 1,  | 512,  | 0  | 
Lutron Machine Map Descriptor
// Client Side Map Descriptors
Map_Descriptors  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Map_Descriptor_Name,  | Data_Array_Name,  | Data_Array_Offset,  | Function,  | Node_name,  | Grafik_Command,  | area,  | Length  | 
Sel_scene_0,  | Analog_Output,  | 0,  | AWT,  | LUT_GRF6_0,  | sel_scene_in_area,  | 0,  | 512  | 
The area field must be used to indicate the start area number that will be associated with the first element of the Data Array specified under Data_Array_Name. Area numbers increase with the Length field in association with increasing offset into the Data Array.