FS-8700-97_Lutron_Machine Manual

Page 14 of 24

4.4.7.Map Descriptor Example 4 - Analog Output 1 (Area Machine)

A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will command an area to a preset scene on the Lutron eLumen panel. Scenes range from 0 to 65535 and area numbers range from 0 to 511

BACNet IP Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Data_Type,

Object_ID,

Length,

Relinquish_Default

SMD000_AO,

Analog_Output,

0,

Server,

Virtual_BCU_11,

AO,

1,

512,

0

Lutron Machine Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Grafik_Command,

area,

Length

Sel_scene_0,

Analog_Output,

0,

AWT,

LUT_GRF6_0,

sel_scene_in_area,

0,

512

The area field must be used to indicate the start area number that will be associated with the first element of the Data Array specified under Data_Array_Name. Area numbers increase with the Length field in association with increasing offset into the Data Array.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com