FS-8700-97_Lutron_Machine Manual

Page 13 of 24

4.4.6.Map Descriptor Example 3 - Binary Input (Area Machine)

A read from the Binary Input Data Array which is shared by a BACNet IP Map Descriptor will return the scene-on state for the given area. The Lutron Machine Map Descriptor regularly polls the eLumen panel to retrieve the scene-on state for the given area. The value returned by the BACNet object is inactive (0) if the off scene is selected and active (1) if any other scene is selected. The off scene numbers range from 0 to 65535 and are preloaded in the Data Array specified under “DA_Lut_List”.

BACNet IP Map Descriptor

//Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Data_Type,

Object_ID,

Length,

Relinquish_Default

SMD00_BI,

Binary_Input,

0,

Server,

Virtual_BCU_11,

BI,

1,

512,

0

Lutron Machine Map Descriptor

//Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name, Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Grafik_Command,

Area,

DA_Lut_List,

DA_Lut_List_Offset,

Length

Area_sts_0,

Binary_Input,

0,

ARCO,

LUT_GRF6_0,

area_sts_offscene,

0,

off_scene,

0,

512

The ARCO function is the same as RDBC except that the Map Descriptor length is taken as the number of areas to poll. The start area number is specified under the “Area” Map Descriptor field. More than one ARCO Map Descriptor may be used to poll two series of area numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 perform the same function as RDBC Map Descriptors with the same length.

The Data Array specified under “DA_Lut_List” must be preloaded with scene numbers as shown below:

//================================================================================

//Binary Input Scenes Setup

//All values are in decimal ( 0 - 65535 )

//Insert the off-scene number in the preload_data_value field

 

Preloads

 

 

 

 

 

 

 

Data_Array_Name ,

Preload_Data_Format ,

Preload_Data_Value ,

Location

 

// Binary Input Object ID 1

 

 

 

 

 

 

 

 

 

 

 

 

off_scene

,

Uint16

,

0

,

0

 

// Binary Input Object ID 2

 

 

 

 

 

 

 

 

 

 

 

 

off_scene

,

Uint16

,

1

,

1

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 13
Image 13
FieldServer FS-8700-97 instruction manual Map Descriptor Example 3 Binary Input Area Machine