4.4.12.Map Descriptor Example 9 - Multistate Output (Zone and Area Machine)

A write to the Multistate Output Data Array which is shared by a BACNet IP Map Descriptor will execute one of multiple scripts. The multiple scripts are specified in the Data Array defined under “DA_Lut_List”. The value written into the Multistate Output Data Array is used as the offset into the Data Array defined under “DA_Lut_List” to retrieve a script number from the Data Array. Script numbers range from 0 to 65535.

BACNet IP Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Data_Type,

Object_ID,

Length,

Relinquish_Default,

SMD00_MO,

MultiSt_Output,

0,

Server,

Virtual_BCU_11,

MO,

1,

512,

0,

Lutron Machine Map Descriptor

//Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

 

Data_Array_Name,

 

Data_Array_Offset,

Function,

Node_name,

Grafik_Command,

DA_Lut_List,

DA_Lut_List_Offset,

Length,

Multi_Scripts_Length

Run_scriptms_0,

 

MultiSt_Output,

 

0,

AWT,

LUT_GRF6_0,

run_script_multi,

Scr_lst_MSO_0,

0,

1,

10

The Multi_Scripts_Length field is used to indicate the maximum size of the Data Array specified under Data_Array_Name. One Map Descriptor per object must be defined with a Multi_Scripts_Length value of one or greater.