Alarm and Faults
. |
|
|
|
|
|
Table 8 |
| Event messages |
|
| |
|
|
|
|
|
|
ID |
|
| Alarm Message | Description/Cause | Action |
|
|
|
|
|
|
001 |
| S1 | SCR SHORT | One or more of the SCRs for Source 1 have shorted and failed. | D, F, A, E |
|
|
|
|
|
|
002 |
| S2 | SCR SHORT | One or more of the SCRs for Source 2 have shorted and failed. | D, F, A, E |
|
|
|
|
|
|
003 |
| S1 | SCR OPEN | One or more of the SCRs for Source 1 is open. | D, F, A, E |
|
|
|
|
|
|
004 |
| S2 | SCR OPEN | One or more of the SCRs for Source 2 is open. | D, F, A, E |
|
|
|
|
| |
005 |
| PRIMARY FAN FAIL | A primary cooling fan has failed and the unit is now being | D, A, E | |
|
|
|
| cooled by a secondary fan, which is not monitored. |
|
006 |
| CONTROL MODULE FAIL | Control logic module has failed. | D, A, E | |
|
|
|
|
| |
007 |
| PWR SPLY DC A FAIL | Power supply DC bus A has failed. | D, A, E | |
|
|
|
|
| |
008 |
| PWR SPLY DC B FAIL | Power supply DC bus B has failed. | D, A, E | |
|
|
|
|
| |
009 |
| PWR SPLY S1 AC FAIL | Power supply Source 1 AC has failed. | D, A, E | |
|
|
|
|
| |
010 |
| PWR SPLY S2 AC FAIL | Power supply Source 2 AC has failed. | D, A, E | |
|
|
|
|
| |
011 |
| PWR SPLY LOGIC FAIL | A power supply module has failed. | D, A, E | |
|
|
|
|
| |
012 |
| OUT VOLT SENSE FAIL | The output volt sense module failed | D, A, E | |
|
|
|
|
|
|
013 |
| S1 | VOLT SENSE FAIL | The Source 1 volt sense module failed. | D, A, E |
|
|
|
|
|
|
014 |
| S2 | VOLT SENSE FAIL | The Source 2 volt sense module failed. | D, A, E |
|
|
|
|
|
|
015 |
| S1 | SCR SENSE FAIL | The Source 1 SCR sense module failed. | D, A, E |
|
|
|
|
|
|
016 |
| S2 | SCR SENSE FAIL | The Source 2 SCR sense module failed. | D, A, E |
|
|
|
|
|
|
017 |
| S1 | CURR SENSE FAIL | The Source 1 SCR current module failed. | D, A, E |
|
|
|
|
|
|
018 |
| S2 | CURR SENSE FAIL | The Source 2 SCR current module failed. | D, A, E |
|
|
|
|
|
|
019 |
| S1 | GATE DRIVE FAIL | The Source 1 gate drive module failed. | D, A, E |
|
|
|
|
|
|
020 |
| S2 | GATE DRIVE FAIL | The Source 2 gate drive module failed. | D, A, E |
|
|
|
|
| |
021 |
| INTERNAL COMM FAIL | Internal CAN communications failed. | D, A, E | |
|
|
|
|
| |
022 |
| EXTERNAL COMM FAIL | Options CAN communications failed. | A, E | |
|
|
|
|
| |
023 |
| CB1 SHUNT TRIP FAIL | CB1 shunt trip failed. | A, E | |
|
|
|
|
| |
024 |
| CB2 SHUNT TRIP FAIL | CB2 shunt trip failed. | D, A, E | |
|
|
|
|
| |
064 |
| HEATSINK OVERTEMP | Heatsink has exceeded the recommended temperature. | A, E | |
|
|
|
|
|
|
067 |
| S1 | UV | Source 1 under voltage, fast detection. | A, E |
|
|
|
|
|
|
068 |
| S1 | UV (RMS) | Source 1 under voltage, slow detection. | L, A, E |
|
|
|
|
|
|
069 |
| S1 | OV | Source 1 over voltage | A, E |
|
|
|
|
|
|
070 |
| S1 | OF/UF | Source 1 over frequency/under frequency | A, E |
|
|
|
|
|
|
071 |
| S1 | FAIL | Source 1 failure. | A, E |
|
|
|
|
|
|
072 |
| S2 | UV | Source 2 under voltage, fast detection. | A, E |
|
|
|
|
|
|
073 |
| S2 | UV (RMS) | Source 2 under voltage, slow detection. | A, E |
|
|
|
|
|
|
074 |
| S2 | OV | Source 2 over voltage. | A, E |
|
|
|
|
|
|
075 |
| S2 | OF/UF | Source 2 over frequency/under frequency. | A, E |
|
|
|
|
|
|
076 |
| S2 | FAIL | Source 2 failure. | A, E |
|
|
|
|
| |
077 |
| S1 OVERCURRENT | Source 1 over current. | A, E | |
|
|
|
|
| |
078 |
| S2 OVERCURRENT | Source 2 over current. | A, E | |
|
|
|
|
|
|
079 |
| S1 | A, F, E | ||
|
|
|
|
|
|
080 |
| S2 | A, F, E | ||
|
|
|
|
| |
081 |
| SOURCES OUT OF SYNC | Source 1 and Source 2 are out of synchronization. | A, E | |
|
|
|
|
| |
082 |
| LOAD ON ALT SOURCE | The output load is running on the alternate source. | A, E | |
|
|
|
|
| |
083 |
| AUTO REXFER INHIBIT | Automatic retransfer is inhibited. | A, E | |
|
|
|
|
|
|