.51 DIA.

PEM NUT

GROUND BUS

INPUT/OUTPUT BUS

FRONT VIEW

RIGHT SIDE VIEW

PEM NUT

NEUTRAL BUS

RIGHT SIDE VIEW

SOURCE 1 INPUT Ø A, Ø B, Ø C

NOTES:

1.ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS).

2.TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH REMOVABLE ACCESS PLATES. REMOVE, PUNCH TO SUIT CONDUIT SIZE, AND REPLACE.

3.CONTROL WIRING AND POWER WIRING MUST BE RUN IN SEPARATE CONDUIT. OUTPUT CABLES SHOULD BE RUN IN A SEPARATE CONDUIT FROM INPUT CABLES.

4.ALUMINUM AND COPPER CLAD ALUMINUM CABLES ARE NOT RECOMMENDED.

5.ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES.

6.HARDWARE KIT IS SUPPLIED FOR INPUT, OUTPUT, NEUTRAL, AND GROUND CABLE CONNECTIONS. KIT INCLUDES 1/2" BOLTS, WASHERS, AND NUTS FOR CONNECTING CABLES TO THE BUS BARS.

7.THE TORQUE REQUIREMENT FOR 1/2"-13 PEM NUTS IS

428INCH-LBS. (48 N-m).

Figure 14 Electrical field connections

27

 

 

SOURCE 1 INPUT Ø A

 

 

 

 

 

SOURCE 2 INPUT

SOURCE 1 INPUT Ø B

 

 

 

 

 

Ø A, Ø B, Ø C

 

 

 

 

 

 

SOURCE 1 INPUT Ø C

 

 

 

 

 

 

NEUTRAL BUS

 

 

 

 

CB1

CB2

 

 

 

 

 

 

 

SOURCE 1

 

SOURCE 2

CB4

CB5

 

CB1

CB2

 

 

 

 

 

 

 

 

 

K1

 

K2

 

NEUTRAL

CB3

 

 

 

 

 

 

K2 K3

CB4

CB3

K1 K3

CB5

BUS

 

SYSTEM OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

Ø A, Ø B, Ø C

 

 

 

 

 

 

FRONT

 

 

 

 

 

GROUND

 

 

 

SYSTEM OUTPUT

 

 

BUS

 

 

 

 

 

SECTION A-A

 

 

ONE-LINE DIAGRAM

 

 

FRONT VIEW

 

 

 

 

SIDE VIEW

 

 

 

 

 

(WITH FRONT PANELS REMOVED)

PS212100

Rev. 3

drawing: 100 – 250 amp Liebert STS2 with single output breaker

Installation Drawings