26

 

(335 MM)

(335 MM)

(396 MM)

(335 MM)

(335 MM)

SEE NOTE (7)

13.2"

13.2"

15.6"

13.2"

13.2"

FOR SPACING

 

 

 

 

BACK WALL

(832 MM) 32.75"

FRONT

SIDE WALL

FRONT FLOOR

(310 MM)

(289 MM)

(817MM)

BRACKET

12.2"

11.4"

32.2"

(107 MM)

(107 MM)

(107 MM)

(107 MM)

4.2"

4.2"

4.2"

4.2"

TOP VIEW

SYSTEM SEISMIC ANCHORING, FIGURE 1

NOTES:

REAR FLOOR

BRACKET

SEE NOTE (2)

FOR SPACING

REAR

CABINET

 

BASE

BRACKET

BACK

 

 

WALL

 

 

APPROX 1/2"

FLOOR LINE

REAR F LOOR

 

 

BRACKET

FLOOR ANCHOR HARDWARE

(NOT SUPPLIED )

FIGURE

2

 

 

 

FRONT DOOR

FRONT

CABINET

 

OF CABINET

BASE

BRACKET

 

HARDWARE

 

 

 

SUPPLIED

 

 

(144 MM)

FLOOR ANCHOR

 

 

5.7"

HARDWARE

 

 

 

NOT SUPPLIED

 

 

FLOOR LINE

FRONT FLOOR

BRACKET

FIGURE 3

Figure 13 Seismic anchor drawing: 800 – 1000 amp Liebert STS2

1. RECOMMENDED

FLOOR

ANCHOR:

1/2"

ITW

RAMSET/RED

HEAD

SELF DRILLING ANCHOR,

ICBO #ER-1372

OR

EQUIVALENT

(NOT

 

(SUPPLIED). FOLLOW MANUFACTURER'S INSTRUCTIONS.

 

 

 

2. POSITION

REAR

FLOOR

BRACKETS

ON FLOOR

AT LEAST

.75"

 

FROM BACK

WALL.

MARK

LOCATION

A ND DRILL

HOLES (FIG. 1)

TO

A MINIMUM DEPTH OF 4.12" INTO THE CONCRETE.

3.INSTALL REAR CABINET BASE BRACKET (FIG. 2) TO EXISTING HOLES ON UNDERSIDE OF UNIT WITH TABS FACING BACK WALL.

USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).

NOTE, LOOSEN LEVELING BOLT LOCKING NUT AND TIGHTEN AFTER BRACKET IS SECURED.

4.INSTALL FRONT CABINET BASE BRACKET (FIG. 3) TO EXISTING

HOLES

ON U NDERSIDE

OF UNIT WITH BENT FLANGE FACING FRONT.

USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).

NOTE,

LOOSEN LEVELING BOLT LOCKING NUT AND TIGHTEN AFTER

BRACKET IS SECURED.

 

5. MOVE

CABINET INTO

P OSITION

W ITH REAR TABS INTO S LOTS OF

FLOOR BRACKET. TABS TO EXTEND AT LEAST 1/2" THROUGH FLOOR

BRACKET

(FIG.

2). THEN

ATTACH

FRONT FLOOR BRACKETS TO FRONT

CABINET

BASE

BRACKET

BUT DO N OT FULLY T IGHTEN HARDWARE.

6. MARK

HOLE LOCATIONS AND REMOVE BRACKETS. DRILL AND INSTALL

FLOOR

BRACKETS.

UNIT

DOOR CAN BE REMOVED

 

FOR BETTER

ACCESS.

REINSTALL

FRONT

FLOOR

BRACKETS

TO FRONT

CABINET

BRACKETS

WITH

SUPPLIED HARDWARE AND TORQUE TO 235 LB-IN (26.5 Nm), (FIG. 3).

 

 

 

7. IF SIDE

WALLS

ARE

PRESENT,

5.0 INCH MINIMUM

D ISTANCE

FROM

EITHER

SIDE WALL

IS REQUIRED.

 

 

 

 

 

 

 

 

 

8. REAR

A ND FRONT

FLOOR

BRACKETS,

AND REAR

AND

FRONT

CABINE T

BASE BRACKETS

ARE

1010

STEEL

AND

APPROX.

.25 INCH

THICK.

 

PS211805

Rev. 0

Installation Drawings

Page 34