Installation Drawings

Figure 20 Liebert STS2 non-automatic circuit breaker schedule

 

 

 

 

 

 

 

 

 

 

 

 

Liebert STS2

 

 

 

 

 

 

 

Ampere

 

 

 

 

Withstand

 

 

Rating, A

Vendor

Type

Ampacity, A

Voltage

Current

 

 

 

 

 

 

200-240V

125K

 

 

100

Square D

HL

150

380-480V

100K

 

 

 

 

 

 

600V

50K

 

 

 

 

 

 

200-240V

125K

 

 

250

Square D

JL

250

380-480V

100K

 

 

 

 

 

 

600V

50K

 

 

 

 

 

 

200-240V

100K

 

 

400

Merlin Gerin

NSJ

400

380-480V

100K

 

 

 

 

 

 

600V

25K

 

 

 

 

 

 

200-240V

100K

 

 

600

Merlin Gerin

NSJ

600

380-480V

100K

 

 

 

 

 

 

600V

25K

 

 

 

 

 

 

200-240V

100K

 

 

800

Square D

PJ

800

380-480V

65K

 

 

 

 

 

 

600V

25K

 

 

 

 

 

 

200-240V

100K

 

 

1000

Square D

PJ

1200

380-480V

65K

 

 

 

 

 

 

600V

25K

 

1.The Liebert STS2 non-automatic breakers are 3-pole, 600VAC rated with magnetic trip only.

2.Upstream devices (by others) must be used to provide overcurrent protection. Upstream overcurrent protection should have ampacity equal to or less than the ampere rating of the static switch.