Specifications

15.0SPECIFICATIONS

This section provides the specifications for the Liebert STS2.

15.1System Configuration

The Liebert STS2 can be set in several different configurations, according to the model and location. The configuration is set at the factory and does not need to be changed by the customer. These config- urations apply to both units, the Color Graphical Display and an LED Display.

15.1.1Frequency

The Liebert STS2 accepts input frequencies of 50 Hz and 60 Hz. The frequency shall be within

± 0.5Hz of the nominal frequency.

15.1.2Input/Output Voltage

The Liebert STS2 models are available to handle various voltages.

The input voltage must be three-phase AC (3 or 4 wire-plus-ground). The Liebert STS2 is designed to accept an input neutral from each source. The neutral is switched in the 4-pole static transfer switch only.

The voltage shall be within ± 10% of the nominal voltage.

The output voltage shall be three-phase AC (3 or 4 wire-plus-ground). Nominal output voltage shall be same as input voltage.

The following table provides nominal voltages, listed according to frequency.

Table 16 Input/output voltage

60Hz

50 Hz

 

 

[L-L/L-N]

[L-L/L-N]

 

 

200/115V

200/115V

 

 

208/120V

208/120V

 

 

220/127V

220/127V

 

 

240/139V

240/139V

 

 

380/220V

380/220V

 

 

400/230V

400/230V

 

 

415/240V

415/240V

 

 

480/277V

 

 

 

600/346V

 

 

 

15.1.3 System Current Ratings

These ratings are based upon continuous switch current rating. These ratings are for all voltages and frequencies. All units are 100% continuous current rated.

Table 17 System current ratings

Current

100

250

400

600

800

1000