Emerson Static Transfer Switch user manual breaker, Drawings

Models: Static Transfer Switch

1 152
Download 152 pages 63.42 Kb
Page 39
Image 39

PEM NUT

.51 DIA.

GROUND BUS

.51 DIA.

INPUT/OUTPUT BUS

FRONT VIEW

RIGHT SIDE VIEW

 

NOTES:

1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS).

2. TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH

REMOVABLE ACCESS PLATES. REMOVE, PUNCH TO SUIT

CONDUIT SIZE, AND REPLACE.

3. CONTROL WIRING AND POWER WIRING MUST BE RUN

IN SEPARATE CONDUIT. OUTPUT CABLES SHOULD BE

RUN IN A SEPARATE CONDUIT FROM INPUT CABLES.

4. ALUMINUM AND COPPER CLAD ALUMINUM CABLES ARE

NOT RECOMMENDED.

5. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL

AND LOCAL ELECTRICAL CODES.

6. HARDWARE KIT IS SUPPLIED FOR INPUT, OUTPUT,

NEUTRAL, AND GROUND CABLE CONNECTIONS. KIT

INCLUDES 1/2" BOLTS, WASHERS, AND NUTS FOR

CONNECTING CABLES TO THE BUS BARS.

Figure 18 Electrical field connections

31

CB1

CB4

SOURCE 1 INPUT

Ø A, Ø B, Ø C

SOURCE 2 INPUT

ØA, Ø B, Ø C

CB2

CB5

GROUND

BUS

SYSTEM OUTPUT

ØA, Ø B, Ø C

CB3

NEUTRAL BUS

FRONT

NEUTRAL BUS RIGHT SIDE VIEW

7. THE TORQUE REQUIREMENT FOR 1/2"-13 PEM NUTS IS

428 INCH-LBS. (48 N-m).

SOURCE 1

INPUT Ø A

SOURCE 1

INPUT Ø B

SOURCE 1

INPUT Ø C

NEUTRAL

BUS

 

 

 

 

SOURCE 1

 

SOURCE 2

 

CB1

 

CB2

 

 

K1

 

K2

 

K2 K3

CB4

CB3

K1 K3

CB5

SYSTEM OUTPUT

drawing: 800 – 1000 amp Liebert STS2 with single output

Installation

FRONT VIEW

SECTION A-A

SIDE VIEW

(WITH FRONT PANELS REMOVED)

 

ONE-LINE DIAGRAM

PS212800

Rev. 2

breaker

Drawings

Page 39
Image 39
Emerson Static Transfer Switch user manual breaker, Drawings