Maintenance

17.0 MAINTENANCE

! WARNING

Only qualified service personnel should perform maintenance on the static switch. Lethal voltages exist inside the unit during normal operation.

The unit is supplied by multiple AC power sources. Disconnect and lock-out all power sources before working inside unit.

Minimal periodic maintenance of the Liebert STS2 is required. As with all electrical distribution com- ponents, the system should be regularly inspected for electrical connection integrity, signs of exces- sive temperatures, dirt accumulation, and proper system operation.

17.1Proper Tightening of Nuts and Bolts

The recommended tightening torque for all nuts and bolts is as shown below, unless otherwise labeled. All power connections are designed to remain at proper torque throughout the lifetime of the unit.

Table 24 Torque tightening

 

Grade 5 -Imperial

Electrical Connections

Bolt Shaft

Grade 8.8 -Metric

With Belleville Washers

 

 

 

 

Size

in-lb

N-m

in-lb

N-m

 

 

 

 

 

10-32

25

3

35

4

 

 

 

 

 

1/4-20

53

6

80

9.0

 

 

 

 

 

5/16-18

107

12

180

20.4

 

 

 

 

 

3/8-16

192

22

240

27.1

 

 

 

 

 

1/2-13

428

48

480

54.3

 

 

 

 

 

17.2Testing the Liebert STS2

The Liebert STS2 includes comprehensive system alarms and fault detection to identify operational problems. To increase the degree of confidence of proper system operation, periodic transfer tests can be easily performed. For instructions for changing the preferred source and switching sources:

For a Color Graphical Display unit, see 10.2 - Manual Transfer / Preferred Source Selection on page 66.

For an LED-equipped unit, see 14.2.2 - Manual Transfer / Preferred Source Selection on page 106.

17.3Changing the Air Filter

A standard furnace filter is installed behind the air intake in the front door. The air intake allows air to circulate to cool the unit. Replace the filter when it becomes dirty and impedes air flow. The fre- quency of changing or cleaning the filter depends on the location in which the unit is located.

The size of the filter is 1 in. x 25 in. x 25 in. (2.54 cm x 63.5 cm x 63.5 cm).