Liebert STS2 Touch Screen Display
Figure 58 Programmable relay board dialog box
2.Select your configuration settings.
•Select STANDARD SET to use the settings configured at the factory. See Go to step 4.
•Select USER DEFINED SET to configure your own settings. Go to step 3.
If you enter a
3.To define your relay board settings:
a.Select a Programming Relay.
b.Select an event you want associated with the relay. That fault is placed in the Relay column.
You can associate up to ten (10) events with one relay. If you do so, you should group the events logically to simplify troubleshooting when an event is triggered.
4.Select SAVE to keep the settings.
5.Select OK for the applicable Programmable Options Board option in the Comm Options dialog box to activate the settings.
Configuring the Liebert IntelliSlot Web/485 Card With Adapter
An optional Liebert IntelliSlot Web/485 Card With Adapter
Ethernet cabling is the responsibility of the customer. Category 5 cabling is required.
See 6.6 - Liebert IntelliSlot® Web/485 Card With Adapter for more information on the Liebert
If the optional Liebert
•Select YES for the Liebert
98