Installation Drawings
Figure 23 Control wiring for remote source selection option
See Note 1
Source 1 | Source 2 |
Preferred | Preferred |
S1 GND | S2 GND |
1 |
2 |
3 |
4 |
5 |
6 |
TB50
Remote Source Selection
NOTES
1.
2.Maximum cable length 500 ft. (152m) with #16 AWG, 300V minimum flexible stranded cable.
3.All control wiring (by others) must be run separate from power wiring . Control wiring runs should not be combined in the same conduit.
4.Refer to Static Transfer Switch control diagram for location of remote source selection opt.
5.All wiring must be in accordance with national and local electrical codes.
PS213007
Rev. 02
36