3.4Altitude

The standard units are designed for full load operation up to 4000 feet (1200 m) above sea level. See Figure 1 for recommended deratings for altitudes greater than 4000 feet (1200 m).

Figure 1 Recommended derating for high altitude operation

Rating (%)

100

98

96

94

92

90

88

86

0

4000

(1200)

4500

(1372)

5000

(1524)

5500

(1676)

6000

(1829)

6500

(1981)

7000

(2134)

7500

(2286)

8000

(2438)

8500

(2591)

9000

(2743)

9500

(2896)

10,000

(3048)

Altitude, Feet (M) Above Sea Level

Operation at full load at a higher altitude can be accommodated in ambient temperatures less than 104°F (40°C) ambient. Figure 2 shows the maximum allowable ambient temperature for full load operation at altitudes above 4000 feet (1200 m).