FS-8700-97_Lutron_Machine Manual

Page 19 of 24

4.4.11.Map Descriptor Example 8 - Analog Input (Zone Machine)

A read from the Analog Input Data Array which is shared by a BACNet IP Map Descriptor will return the intensity to which a given zone is set on the Lutron eLumen panel. The Lutron Machine Map Descriptor regularly polls the Lutron eLumen panel to retrieve the zone intensities. The intensity value returned is scaled to a percentage value (0 to 100%). Zone numbers range from 0 to 511.

BACNet IP Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

Node_name,

Data_Type,

Object_ID,

Length,

Relinquish_Default

SMD00_AI,

Analog_Input,

0,

Server,

Virtual_BCU_11,

AI,

1,

512,

0

Lutron Machine Map Descriptor

//Client Side Map Descriptors

Map_Descriptors

 

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name,

Data_Array_Offset,

Function,

 

Node_name,

 

Grafik_Command,

zone,

Length

Zone_inta_0,

Analog_Input,

0,

ARCO,

 

LUT_GRF6_0,

 

zone_intensity,

0,

512

The ARCO function is the same as RDBC except that the length of the Map Descriptor is taken as the number of zones to poll. The start zone number is specified under the “zone” Map Descriptor field. More than one ARCO Map Descriptors may be used to poll two series of zone numbers, eg. from 5-10 and from 300-340. ARCO Map Descriptors with Length 1 fullfil the same function as RDBC Map Descriptors with the same length.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 19
Image 19