FieldServer FS-8704-06 instruction manual Client Side Node Descriptors

Models: FS-8704-06

1 24
Download 24 pages 58.62 Kb
Page 6
Image 6

FS-8704-06 BACnet IP Driver Manual

Page 6 of 24

4.2.Client Side Connection Descriptions

 

Section Title

 

 

 

 

 

 

Adapter

 

 

 

 

 

 

Column Title

 

Function

 

Legal Values

 

 

Adapter

Adapter Name

 

N1, N24

 

Protocol

 

Specify protocol used

 

BACnet_IP

 

Poll_Delay*

Time between internal polls

 

0-32000s; 0.25s

 

IP_Port*

 

Specify the UDP port that will be used to

 

Any legal IP port value

 

 

communicate with other BACnet Client devices.

(1 - 65535); 47808

 

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

// Client Side Connections

 

 

 

 

Connections

 

 

 

 

 

 

Adapter,

 

Protocol,

Poll_Delay

 

 

N1,

 

Bacnet_IP,

0.500s

 

 

4.3.Client Side Node Descriptors

 

Section Title

 

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

 

Column Title

 

Function

 

 

Legal Values

 

 

Node_Name

Provide name for Node

 

 

Up to 32 alphanumeric

 

 

 

characters

 

 

 

 

 

 

 

Node_ID

 

BACnet station address of physical Server

1 - 4194303

 

 

 

node

 

 

 

 

 

 

 

 

 

 

Protocol

 

Specify protocol used

 

BACnet_IP

 

Adapter

 

Specify port Adapter used

 

 

N1, N24

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

// Client Side Nodes

 

 

 

 

 

Nodes

 

 

 

 

 

 

 

Node_Name,

 

Node_ID,

Protocol,

 

Adapter

 

 

BCU_01,

 

1,

Bacnet_IP,

 

N1

 

4Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com