FieldServer FS-8704-06 FieldServer Related Map Descriptor Parameters, Timing Parameters

Models: FS-8704-06

1 24
Download 24 pages 58.62 Kb
Page 7
Image 7

FS-8704-06 BACnet IP Driver Manual

Page 7 of 24

4.4.Client Side Map Descriptors

4.4.1.FieldServer Related Map Descriptor Parameters

 

Section Title

 

 

 

 

 

Map Descriptors

 

 

 

 

 

Column Title

 

Function

 

Legal Values

 

Map_Descriptor_Name

Name of this Map Descriptor

 

Up to 32 alphanumeric

 

 

characters

 

 

 

 

 

 

 

 

Name of Data Array where

 

One of the Data Array names

 

Data_Array_Name

 

data is to be stored in the

 

 

 

 

from “Data Array” section above

 

 

 

FieldServer

 

 

 

 

 

 

 

Data_Array_Offset

 

Starting location in Data Array

0 to (“Data_Array_Length” -1)

 

Function

 

Function of Client Map

 

Rdbc, Wrbc, Wrbx, Ars

 

 

Descriptor

 

 

 

 

 

 

4.4.2.Driver Related Map Descriptor Parameters

Section Title

 

 

Map Descriptors

 

 

Column Title

Function

Legal Values

 

 

One of the Node_Names

Node_Name

Name of remote Server Node.

specified in “Client Side Node

 

 

Descriptors” above

Data_Type

Data type

AI, AO, AV, BI, BO, BV, MI,

MO, MV5

 

 

 

Object_ID

Address of the object

0, 1, 2, 3, …4194303

Property*

The BACnet property to be read

Present_Value

 

 

 

Data_Array_Low_Scale*

Scaling zero in Data Array

-32767 to 32767, 0

 

 

 

Data_Array_High_Scale*

Scaling max in Data Array

-32767 to 32767, 100

 

 

 

Node_Low_Scale*

Scaling zero in Connected Node

-32767 to 32767, 0

Node_High_Scale*

Scaling max in Connected Node

-32767 to 32767, 100

 

Allows the driver to specify the

 

Write_Priority*

write priority used to write an

1..16, 16

 

output. See also Appendix B.2

 

 

This over-writes the Data_Type

 

Custom Type

with a numerical value for the

1..1023

Data_Type. e.g. Analog Value =

 

 

 

2

 

 

This over-writes the Property with

 

Custom_Prop

a numerical value for the

1..4194303

 

property. e.g. Present Value = 85

 

4.4.3.Timing Parameters

Section Title

 

 

Map Descriptors

 

 

Column Title

Function

Legal Values

Scan_Interval*

Rate at which data is polled

0-32000s, 2s

5Refer to Appendix A.1 for further information.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Page 7
Image 7
FieldServer FS-8704-06 FieldServer Related Map Descriptor Parameters, Driver Related Map Descriptor Parameters