Ventilation requirements (United Kingdom only)

10

Installation instructions

Ventilation requirements (United Kingdom only)

The appliance should be installed in a room or space with an air supply in accordance with BS 5440:2 2000.

For rooms with a volume of less than 5 m3, permanent ventilation through a free area of at least 100 cm2 will be required.

For rooms with a volume between 5 m3 and 10 m3, permanent ventilation through a free area of at least 50 cm2 will be required, unless the room has a door which opens directly to the outside air, in which case no permanent ventilation is required.

For rooms with a volume greater than 10 m3, no permanent ventilation is required.

Important!

Regardless of room size, all rooms containing the appliance must have direct access to the outside air via an openable window or equivalent.

Where there are other fuel-burning appliances in the same room, BS 5440-2: 2000 should be consulted to determine the correct amount of free area ventilation requirements.

The above requirements also allow for use of a gas oven and grill, but you need to consult a qualified engineer if there are other gas-burning appliances in the same room.