PRODUCT SPECIFICATIONS

FAN PERFORMANCE DATA

FIGURE 4. FAN CURVE - PCB 090

SUPPLY FAN PERFORMANCE - PCB090

 

 

 

 

 

EXTERNAL STATIC PRESSURE (INCHES W.C.) SEE NOTE (3)

 

 

 

 

CFM

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2600

669

0.44

816

0.59

916

0.75

1004

0.92

1084

1.09

1157

1.28

1226

1.47

1291

1.67

2800

734

0.53

847

0.69

944

0.85

1030

1.03

1109

1.21

1181

1.40

1249

1.60

1312

1.91

3000

770

0.62

877

0.79

973

0.97

1053

1.15

1135

1.34

1206

1.54

1273

1.75

1336

1.96

3200

807

0.73

909

0.91

1002

1.10

1086

1.29

1162

1.49

1232

1.70

1298

1.91

1360

2.12

3400

845

0.85

942

1.04

1032

1.24

1114

1.44

1159

1.65

1259

1.87

1324

2.09

1384

2.31

Notes:

Selections in ITALICS require a field drive change. See following table below for drive ranges.

Table includes all internal pressure drops including cabinet losses. See Pressure Drops table that must be considered as part of external static pressure drop.

DO NOT SELECT IN SHADED AREAS (FOR INTERPOLATION ONLY).

SUPPLY FAN DRIVE DATA - PCB090

 

 

MOTOR SHEAVE - ADJUSTABLE

FACTORY SETTING

 

 

 

 

 

FAN SHEAVE - FIXED

2 TURNS OPENS

 

 

MOTOR SHEAVE TURNS OPEN

 

0

1

2

3

4

5

FAN RPM

2.0 HP MOTOR

 

1209

1146

1082

1018

955

891

Note: Allow ±5% variation in blower RPM due to pulley manufacturing tolerances.

Conversion Factor:

1 CFM = 0.472 L/S

1” W.C. = 2.5 M Bar 1 HP = 0.747 kW

SS-PCB50