Franklin SS-PCB50 Product Specifications, Nomenclature, Pcb, PCB090-5, PCB120-5, PCB180-5

Models: Self-Contained Package Air Conditioner SS-PCB50

1 12
Download 12 pages 17.02 Kb
Page 2
Image 2
PRODUCT SPECIFICATIONS

PRODUCT SPECIFICATIONS

SPECIFICATIONS

 

PCB090-5

PCB120-5
PCB180-5

Total Cooling - BTU/h (kW)

88,400 (25.9)

118,600 (34.8)

172,000

(50.4)

Sensible Cooling - BTU/h¹ (kW)

67,100 (19.7)

89,200 (26.1)

131,000

(38.4)

EER²

8.9

9.7

8.5

Indoor Blower (Qty.)

2

2

2

 

Type

Belt

Belt

Belt

Size - D x W (mm)

12 x 12 (305 x 305)

12 x 15 (305 x 381)

12 x 15 (305 x 381)

Motor Horsepower (kW)

2 (1.49)

3 (2.24)

5 (3.73)

Indoor CFM Nominal (L/S)

3000 (1416)

4000 (1888)

5600 (2643)

Evaporator Coil (Qty.)

1

1

1

 

Face Area - Ft.² (m²)

9.3 (0.86)

14.0 (1.3)

14.0 (1.3)

Rows/FPI (FPM)

3/16 (630)

3/16 (630)

3/16 (630)

Tube Diameter (mm)/Material

3/8” (9.5)/Copper

3/8” (9.5)/Copper

3/8” (9.5)/Copper

 

 

16” x 25” x 2”

16” x 25” x 2”

Filter Size/Qty. (mm)

25” x 25” x 2”

(406 x 635 x 51)/3

(406 x 635 x 51)/3

(635 x 635 x 8.51)/3

20” x 25” x 2”

20” x 25” x 2”

 

 

 

(508 x 635 x 51)/3

(508 x 635 x 51)/3

 

 

 

 

 

Outdoor Fan (Qty.)

2

2

4

 

Fan Diameter (mm)

24” (610)

24” (610)

22” (559)

Motor Horsepower (kW)

1/2 (0.37)

1/2 (0.37)

1/2 (0.37)

Outdoor CFM Nominal (L/S)

4300 (2030)

6100 (2880)

7000 (3300)

Condenser Coil (Qty.)

1

1

1

 

Face Area Total - Ft.² (m²)

15.6 (1.45)

23.8 (2.21)

23.8 (2.21)

Rows/FPI (FPM)

2/21 (827)

2/21 (827)

3/16 (630)

Tube Diameter (mm)/Material

3/8 (9.5)/Copper

3/8 (9.5)/Copper

3/8 (9.5)/Copper

Number of Compressors

2

2

3

 

Volts-Phase

380-415-3

380-415-3

380-415-3

Compressor RLA/LRA

6.7/47.5

9.5/73.0

9.5/73.0

Blower FLA - Indoor/Outdoor

3.4/1.7

4.2/1.7

7.3/1.7

Minimum Circuit Ampacity³

23.6

31.3

49.5

Maximum Fuse Size

30

50

60

 

Ship Weight - lbs. (kg)

990 (449.5)

1215 (551.6)

1460 (662.8)

¹Sensible capacity is gross, with no deduction for indoor motor heat ² BTU/Watt @ 80/67°F (26.7/19.4°C) inside - 95°F (35°C) outside air

³ Wire size should be in accordance with Local Electrical Codes. Extensive wire runs will require larger wire sizes.

NOMENCLATURE

PCB 090 - 5

ELECTRICAL DESIGNATOR

5 - 380/415 VAC, 3ph, 50Hz

NOMINAL COOLING CAPACITY

090 - 90,000 BTU/h

120 - 120,000 BTU/h

180 - 180,000 BTU/h

UNIT TYPE

PCB - Package Cool

2

SS-PCB50

Page 2
Image 2
Franklin SS-PCB50 specifications Product Specifications, Nomenclature, Pcb, PCB090-5, PCB120-5, PCB180-5