PRODUCT SPECIFICATIONS
FAN PERFORMANCE DATA (CONT.)
COMPONENT PRESSURE DROPS
MODEL | CFM | WET COIL | ELEC. HEAT | MED. EFF. FILTERS | ECONO. RETURN AIR DAMP- | |
ER | ||||||
|
|
|
|
| ||
| 2600 | 0.06 | 0.03 | 0.03 | 0.14 | |
090 | 3000 | 0.06 | 0.04 | 0.04 | 0.14 | |
| 3400 | 0.07 | 0.05 | 0.05 | 0.18 | |
| 3600 | 0.05 | 0.05 | 0.03 | 0.14 | |
120 | 4000 | 0.05 | 0.06 | 0.04 | 0.14 | |
| 4400 | 0.05 | 0.08 | 0.04 | 0.14 | |
| 5000 | 0.13 | 0.10 | 0.06 | 0.18 | |
180 | 5400 | 0.13 | 0.12 | 0.06 | 0.21 | |
| 5600 | 0.16 | 0.13 | 0.08 | 0.23 |
COOLING CAPACITY DATA
PCB090-5 (SI UNITS)
INDOOR |
|
|
|
|
| CONDENSER AIR TEMPERATURE |
|
|
|
|
| ||||||
AIR |
| 23.9°C |
|
| 29.4°C |
|
| 35.0°C |
|
| 40.6°C |
|
| 46.1°C |
| ||
L/S | WB | Total | Sens | Kw | Total | Sens | Kw | Total | Sens | Kw | Total | Sens | Kw | Total | Sens | Kw | |
Cap. | Cap. | Cap. | Cap. | Cap. | Cap. | Cap. | Cap. | Cap. | Cap. | ||||||||
|
|
|
|
|
|
| |||||||||||
| 22.2 | 32.77 | 15.48 | 8.36 | 30.67 | 14.52 | 9.29 | 28.56 | 13.56 | 10.23 | 26.46 | 12.60 | 11.17 | 24.35 | 11.64 | 12.10 | |
1203 | 19.4 | 30.23 | 18.70 | 7.82 | 28.17 | 17.90 | 8.73 | 26.11 | 17.10 | 9.64 | 24.05 | 16.31 | 10.55 | 21.99 | 15.51 | 11.46 | |
16.7 | 27.52 | 23.00 | 7.46 | 26.07 | 21.73 | 8.30 | 24.62 | 20.45 | 9.14 | 23.17 | 19.18 | 9.98 | 21.72 | 17.91 | 10.82 | ||
| |||||||||||||||||
| 13.9 | 26.59 | 24.96 | 7.18 | 24.98 | 23.20 | 8.06 | 23.38 | 21.43 | 8.94 | 21.77 | 19.67 | 9.83 | 20.17 | 17.91 | 10.71 | |
| 22.2 | 34.17 | 17.16 | 8.63 | 31.91 | 16.15 | 9.58 | 29.65 | 15.14 | 10.53 | 27.39 | 14.14 | 11.48 | 25.13 | 13.13 | 12.43 | |
1416 | 19.4 | 31.36 | 21.95 | 8.08 | 29.28 | 20.81 | 9.01 | 27.20 | 19.66 | 9.93 | 25.12 | 18.52 | 10.86 | 23.03 | 17.38 | 11.78 | |
16.7 | 28.62 | 26.83 | 7.53 | 26.96 | 25.02 | 8.49 | 25.30 | 23.20 | 9.44 | 23.65 | 21.39 | 10.40 | 21.99 | 19.58 | 11.35 | ||
| |||||||||||||||||
| 13.9 | 28.62 | 26.83 | 7.53 | 26.96 | 25.02 | 8.49 | 25.30 | 23.20 | 9.44 | 23.65 | 21.39 | 10.40 | 21.99 | 19.58 | 11.35 | |
| 22.2 | 35.01 | 18.42 | 8.82 | 32.73 | 17.46 | 9.77 | 30.46 | 16.50 | 10.73 | 28.18 | 15.54 | 11.69 | 25.90 | 14.59 | 12.64 | |
1628 | 19.4 | 32.19 | 24.67 | 8.28 | 30.10 | 23.35 | 9.21 | 28.00 | 22.04 | 10.14 | 25.91 | 20.72 | 11.07 | 23.81 | 19.40 | 11.99 | |
16.7 | 30.24 | 28.49 | 7.89 | 28.44 | 26.54 | 8.86 | 26.64 | 24.60 | 9.84 | 24.84 | 22.65 | 10.81 | 23.03 | 20.71 | 11.78 | ||
| |||||||||||||||||
| 13.9 | 30.24 | 28.49 | 7.89 | 28.44 | 26.54 | 8.86 | 26.64 | 24.60 | 9.84 | 24.84 | 22.65 | 10.81 | 23.03 | 20.71 | 11.78 |
Sensible heat capacities shown are based on 26.7°C DB entering air at the evaporator coil. For sensible heat capacities at other than 26.7°C DB, deduct 44.32 W per 47 L/S of evaporator coil air for each degree below 26.7°C, or add 44.32 W per 47 L/S of evaporator coil air per degree above 26.7°C.
PCB090-5 (ENGLISH UNITS)
INDOOR |
|
|
|
|
| CONDENSER AIR TEMPERATURE |
|
|
|
|
| |||||||
AIR |
|
| 75°F |
|
| 85°F |
|
| 95°F |
|
| 105°F |
|
| 115°F |
| ||
SCFM | WB | Total | Sens | Kw | Total | Sens | Kw | Total | Sens | Kw | Total | Sens | Kw | Total | Sens | Kw | ||
Kbtuh | Kbtuh | Kbtuh | Kbtuh | Kbtuh | Kbtuh | Kbtuh | Kbtuh | Kbtuh | Kbtuh | |||||||||
|
|
|
|
|
|
|
| |||||||||||
|
| 72 | 111.8 | 52.8 | 8.36 | 104.6 | 49.6 | 9.29 | 97.5 | 46.3 | 10.23 | 90.3 | 43.0 | 11.17 | 83.1 | 39.7 | 12.10 | |
2550 |
| 67 | 103.2 | 63.8 | 7.82 | 96.1 | 61.1 | 8.73 | 89.1 | 58.4 | 9.64 | 82.1 | 55.6 | 10.55 | 75.0 | 52.9 | 11.46 | |
| 62 | 93.9 | 78.5 | 7.46 | 89.0 | 74.1 | 8.30 | 84.0 | 69.8 | 9.14 | 79.1 | 65.5 | 9.98 | 74.1 | 61.1 | 10.82 | ||
|
| |||||||||||||||||
|
| 57 | 90.7 | 85.2 | 7.18 | 85.2 | 79.1 | 8.06 | 79.8 | 73.1 | 8.94 | 74.3 | 67.1 | 9.83 | 68.8 | 61.1 | 10.71 | |
|
| 72 | 116.6 | 58.5 | 8.63 | 108.9 | 55.1 | 9.58 | 101.2 | 51.7 | 10.53 | 93.5 | 48.2 | 11.48 | 85.7 | 44.8 | 12.43 | |
3000 |
| 67 | 107.0 | 74.9 | 8.08 | 99.9 | 71.0 | 9.01 | 92.8 | 67.1 | 9.93 | 85.7 | 63.2 | 10.86 | 78.6 | 59.3 | 11.78 | |
| 62 | 97.6 | 91.6 | 7.53 | 92.0 | 85.4 | 8.49 | 86.3 | 79.2 | 9.44 | 80.7 | 73.0 | 10.40 | 75.0 | 66.8 | 11.35 | ||
|
| |||||||||||||||||
|
| 57 | 97.6 | 91.6 | 7.53 | 92.0 | 85.4 | 8.49 | 86.3 | 79.2 | 9.44 | 80.7 | 73.0 | 10.40 | 75.0 | 66.8 | 11.35 | |
|
| 72 | 119.5 | 62.9 | 8.82 | 111.7 | 59.6 | 9.77 | 103.9 | 56.3 | 10.73 | 96.2 | 53.0 | 11.69 | 88.4 | 49.8 | 12.64 | |
3450 |
| 67 | 109.9 | 84.2 | 8.28 | 102.7 | 79.7 | 9.21 | 95.6 | 75.2 | 10.14 | 88.4 | 70.7 | 11.07 | 81.3 | 66.2 | 11.99 | |
| 62 | 103.2 | 97.2 | 7.89 | 97.0 | 90.6 | 8.86 | 90.9 | 83.9 | 9.84 | 84.7 | 77.3 | 10.81 | 78.6 | 70.7 | 11.78 | ||
|
| |||||||||||||||||
|
| 57 | 103.2 | 97.2 | 7.89 | 97.0 | 90.6 | 8.86 | 90.9 | 83.9 | 9.84 | 84.7 | 77.3 | 10.81 | 78.6 | 70.7 | 11.78 |
Sensible heat capacities shown are based on 80°F DB entering air at the evaporator coil. For sensible heat capacities at other than 80°F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree below 80°F, or add 84 BTU/h per 100 CFM of evaporator coil air per degree above 80°F.
8 |