Franklin SS-PCB50 PCB180-5ENGLISH UNITS, Evaporator Motor Heat, Product Specifications, BTU/h KW

Models: Self-Contained Package Air Conditioner SS-PCB50

1 12
Download 12 pages 17.02 Kb
Page 10
Image 10
PCB180-5 (ENGLISH UNITS)

PRODUCT SPECIFICATIONS

COOLING CAPACITY DATA (CONT.)

PCB180-5 (ENGLISH UNITS)

INDOOR

 

 

 

 

 

CONDENSER AIR TEMPERATURE

 

 

 

 

 

AIR

 

 

75°F

 

 

85°F

 

 

95°F

 

 

105°F

 

 

115°F

 

SCFM

WB

Total

Sens

Kw

Total

Sens

Kw

Total

Sens

Kw

Total

Sens

Kw

Total

Sens

Kw

Kbtuh

Kbtuh

Kbtuh

Kbtuh

Kbtuh

Kbtuh

Kbtuh

Kbtuh

Kbtuh

Kbtuh

 

 

 

 

 

 

 

 

 

 

72

219.0

100.8

16.42

205.3

95.6

18.63

191.7

90.4

20.83

178.0

85.1

23.04

164.4

79.9

25.25

4760

 

67

202.0

121.4

15.36

188.6

117.7

17.50

175.2

113.9

19.63

161.8

110.2

21.76

148.4

106.5

23.89

 

62

183.8

149.6

14.67

174.5

142.9

16.64

165.2

136.3

18.61

155.9

129.6

20.59

146.6

123.0

22.56

 

 

 

 

57

177.6

162.6

14.10

167.2

152.7

16.15

156.9

142.8

18.21

146.5

132.9

20.27

136.1

123.0

22.33

 

 

72

228.3

111.6

16.97

213.6

106.3

19.21

199.0

100.9

21.45

184.3

95.5

23.68

169.6

90.1

25.92

5600

 

67

209.5

142.7

15.87

196.0

136.9

18.05

182.5

131.0

20.22

169.0

125.2

22.40

155.5

119.3

24.46

 

62

191.1

174.8

14.77

180.5

164.7

17.00

169.8

154.6

19.23

159.1

144.5

21.46

148.4

134.4

23.68

 

 

 

 

57

191.1

174.8

14.77

180.5

164.7

17.00

169.8

154.6

19.23

159.1

144.5

21.46

148.4

134.4

23.68

 

 

72

233.9

119.7

17.33

219.1

114.8

19.59

204.4

109.9

21.85

189.6

105.0

24.11

174.9

100.1

26.37

6440

 

67

215.1

160.4

16.27

201.5

153.6

18.46

187.9

146.8

20.64

174.3

140.0

22.83

160.7

133.2

25.01

 

62

202.0

185.6

15.49

190.4

174.7

17.76

178.8

163.9

20.03

167.1

153.0

22.30

155.5

142.1

24.57

 

 

 

 

57

202.0

185.6

15.49

190.4

174.7

17.76

178.8

163.9

20.03

167.1

153.0

22.30

155.5

142.1

24.57

Sensible heat capacities shown are based on 80 °F DB entering air at the evaporator coil. For sensible heat capacities at other than 80 °F DB, deduct 84 BTU/h per 100 CFM of evaporator coil air for each degree below 80 °F, or add 84 BTU/h per 100 CFM of evaporator coil air per degree above 80 °F.

EVAPORATOR MOTOR HEAT

Horsepower/(kW)

BTU/h (KW)

 

 

2 (1.49)

4400 (1.29)

 

 

3 (2.24)

6200 (1.82)

 

 

5 (3.73)

10,500 (3.08)

 

 

10

SS-PCB50