Friedrich 36, 24, 60, 18, 49, 42, 30, 000 Electrical Grounding Power Supply, Cooling and Fan

Models: 49 24 000 42 36 18 60 30

1 20
Download 20 pages 10.8 Kb
Page 12
Image 12

2) Electrical

DANGER: Electrical shock hazard. Turn OFF electric power at the fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before connecting line voltage. Failure to do so can result in property damage, personal injury and/or death.

A. Grounding

CAUTION: The unit must be electrically wired and grounded in accordance with all state and local codes, national electric code, and NFPA 70. Unit and controls will NOT operate unless properly grounded. A ground lug is provided for ground connection. Use only approved copper wire and connectors from unit to service panel.

B. Power Supply

NOTE: Line voltage circuit is completely factory wired. Make all line voltage connections inside circuit breaker junction box. The circuit breakers or fuses used for branch circuit protection should be UL recognized. If circuit breakers are used, the circuit breaker for the compressor circuit must have a UL HACR rating. If fuses are used, the fuse for the compressor circuit MUST be time delay type.

CAUTION: Units are dual voltage rated 208-230/1/60. The 24V control transformer must be connected for either 208V or 240V power source for proper operation. Line voltage must not exceed 253V or go below 197V. The transformer connection must be changed for 208V operation.

Depending on auxiliary heater size, unit must be supplied with 2 or 3 separate 208V or 240V circuits from structure’s fuse box or service panel. Each circuit is internally connected to a circuit breaker located in the unit control box located at the front center of the unit. Refer to Table 4 and Table 5 for required circuits and recommended wire size for each circuit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minim um Circuit

 

 

 

Maxim um Fuse2 or

Cooling and Fan

 

Model

 

Com pressor Am ps

Outdoor Fan Am ps

 

Indoor Fan Am ps

Am pacity

Minim um Wire Size 1

Breaker Size Am ps

Circuit Data

V(E,H)B18

 

9.3

 

 

1.4

 

 

1.0

 

 

14.0

12

 

 

20

V(E,H)B24

 

11.4

 

1.4

 

 

1.0

 

 

16.7

12

 

 

25

V(E,H)B30

 

15.0

 

2.2

 

 

1.8

 

 

22.8

10

 

 

30

V(E,H)B36

 

17.9

 

3.0

 

 

2.5

 

 

27.9

8

 

 

40

V(E,H)B42

 

20.4

 

4.5

 

 

3.0

 

 

33.0

8

 

 

50

 

V(E,H)B49

 

26.4

 

5.0

 

 

3.0

 

 

41.0

6

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

V(E,H)B60

 

32.1

 

5.0

 

 

3.1

 

 

49.0

6

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data

Heater Size

 

Chassis

 

 

 

Ckt #1

 

Ckt #1 Wire

Ckt #1 Max.

Ckt #2 & 33

 

Ckt #2 & 33

Ckt #2 & 33

Ckt #2 & 33

 

(KW)

 

Available

 

Ckt #1 Am ps

Am pacity

 

 

Size1

Fuse2

Am ps

 

Am pacity

Wire Size 1

Max. Fuse2

 

5.0

 

18/24

 

20.8

 

26.0

 

10

 

30

N/A

 

N/A

N/A

N/A

 

Strip

 

 

 

 

 

 

 

10.0

 

18/24/30/36/42

 

41.6

 

52.0

 

6

 

60

N/A

 

N/A

N/A

N/A

 

15.0

 

30/36/42/48

 

20.8

 

26.0

 

10

 

30

41.6

 

52.0

6

60

 

Heat

 

 

 

 

 

 

 

20.0

 

48/60

 

41.6

 

52.0

 

6

 

60

41.6

 

52.0

6

60

 

25.0

 

60

 

20.8

 

26.0

 

10

 

30

41.6

 

52.0

6

60

 

 

 

 

 

 

 

 

1If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetalic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-30. If other than uncoated (non- plated), 60°C or 75°C (140°F or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

2Time-delay fuse.

3Circuit #3 is only used for 25kw heater.

Heat Pump

 

(Field Wiring)

Heat Pump

Auxiliary

Heater #1

(Field Wiring)

Auxiliary

Heater #1

Ground

 

 

 

(Field Wiring)

 

 

 

 

 

Auxiliary

 

Ground Lug

Auxiliary Heater #2

Heater #2

 

 

 

 

(Field Wiring)

 

 

Line Voltage And Ground Connections

Unit Wiring with VPDB1 Distribution Block

12

Page 12
Image 12
Friedrich 36, 24, 60, 18, 49, 42, 30, 000 operation manual Electrical Grounding Power Supply, Cooling and Fan