C. Indoor-Air (Conditioned Supply Air) System

The VEB/VHB series unit may be applied in either a free return air configuration or a ducted return air configuration. The supply air path is intended to be ducted. The design and construction of the indoor-air system must provide adequate air distribution to ensure comfort levels throughout the structure.

The combined pressure losses of the return and supply air paths must not exceed the external static capabilities of the system at the design airflow (See Table 2).

If the unit is installed in a closet behind a door and the return air louver or grille is directly opposite the unit RA opening, 2- in. clearance is required between the front of the unit and the back side of the louver or grille. If the louver or grille is located elsewhere on the door so it is not directly in front of the RA opening, a minimum of 7-in. clearance is required between the front of the unit and the back side of the door. The minimum "net free open area" required for the RA louver or grille is listed in Table 2.

Indoor Fan Performance

Table 2

 

Indoor Blower Air Flow, SCFM (ARI RATED as shown)

 

RA Grille Minimum Net

Model

ESP

0.1

0.2

0.3

0.4

 

0.5

Free Open Area (Sq. In.)

 

 

 

 

 

 

 

 

 

VE/HB18

Indoor

850

750

640

550

 

450

250

VE/HB24

Indoor

980

890

800

720

 

650

300

VE/HB30

Indoor

1120

1070

1000

940

 

830

375

VE/HB36

Indoor

1220

1120

1050

990

 

860

400

VE/HB42

Indoor

1570

1510

1470

1400

 

1350

525

VE/HB49

Indoor

1670

1610

1570

1500

 

1450

525

VE/HB60

Indoor

1980

1920

1860

1800

 

1700

675

Note: Italic indicates performance outside the required operating window of +/- 10% of rated SCFM. All values are wet coil with filter installed.

Figure 10

Return Air Options

Front Free

Front Ducted

Side Ducted

Return

Return

Return

NOTE: Ducted return air configurations require field fabrication of a duct-mounted filter box. Filters are not supplied with units configured for ducted return.