Williams 3003611, 3003612, 2203611, 2203612 Troubleshooting Gravity Direct Vent Wall Furnace

Models: 3003612 3003611 2203612 1403612 2203611 1403611

1 26
Download 26 pages 38.41 Kb
Page 21
Image 21
Troubleshooting Gravity Direct Vent Wall Furnace

Troubleshooting Gravity Direct Vent Wall Furnace

SYMPTOM

POSSIBLE

CAUSE

1. Pilot will

not stay lit after

A. Thermocouple

or

gen-

carefully

following

erator

producing

insuffi-

lighting

instructions.

cient

millivoltage.

 

 

 

B. Loose or dirtythermocou-

 

 

pie or generator connec-

 

 

tions

at gas valve.

 

 

C. Thermocouple or gen-

 

 

erator

defective.

 

D. Grounded thermostat lead wire (Wall ther- mostat model).

CORRECTIVE ACTION

Check pilot flame - must impinge on thermocou- pie or generator. Be sure thermocouple or generator is fully inserted in bracket. Make sure pilot lighting door is tightly closed.

Clean and/or tighten thermocouple or generator connections at valve.

Check thermocouple with millivolt meter. Should generate approximately 30 millivolts when not con- nected to load. When connected to load, should

generate approximately 14 millivolts; if below 7 millivolts, replace.

Check generator with millivolt meter. Take reading at generator terminals of valve with pilot burning and thermostat contacts closed. Should be 140 millivolts or more.

Remove thermostat lead wires from valve terminals. If pilot now stays lit, trace thermostat wiring circuit for a ground. May be grounded to furnace or gas supply.

2.Pilot burning - no gas to main burner.

3.Burner comes "On" but goes "Off" after operating for no apparent reason.

E. Thermomagnet pilot safety defective.

A.Manual valve not turned to "On" position after lighting pilot.

B.Temperature dial or ther- mostat not turned to a position calling for heat.

C.Plugged burner orifice.

DTemperature dial out of

calibration. (Bulb control model.)

E.Mis-wired or broken ther- mostat wires. Defective

thermostat. 0Nail thermo- stat model.

FPilot generator may not be generating sufficient millivoltage to open valve.

G. Defective valve.

A. Tubes not properly installed.

B. Furnace may be overrated.

g21--

Replace gas valve after above is checked out.

Turn gas valve knob to "On" position.

Set temperature dial or thermostat to a position call- irtg for heat.

Check - clean or replace.

See valve manufacturer's instructions.

Check connections at valve terminals. Jumper across thermostat terminals on valve - if valve

operates check thermostat wires.

See 1A above.

Replace.

Check vent tube and air inlet tube. Follow installa- tion instructions. Be sure joints are tight and both tubes are in place. Use only tubes furnished. Do not extend tubes beyond original length.

Check for high pressure at valve - see rating plate for specified minimax supply pressure. Check burner orifice.

(continued next page)

Page 21
Image 21
Williams 3003611, 3003612, 2203611, 2203612, 1403611, 1403612 owner manual Troubleshooting Gravity Direct Vent Wall Furnace