Gas Supply & Piping
Gas control valve, within the furnace, is shipped with a seal over gas inlet tapping. Do not remove this seal until ready to connect piping.
WARNING
DANGER OF PROPERTY DAMAGE,
BODILY INJURY OR DEATH.
MAKE SURE THE FURNACE IS EQUIPPED TO OPERATE ON THE TYPE OF GAS AVAILABLE. MODELS DESIGNATED AS NATURAL GAS ARE TO BE USED WITH NATURAL GAS ONLY. FURNACE DESIGNATED FOR USE WITH LIQUEFIED
PETROLEUM (L.R) GAS HAVE ORIFICES SIZED FOR COMMERCIALLY PURE PROPANE GAS. THEY CANNOT BE USED WITH BUTANE OR A MIXTURE OF BUTANE AND PROPANE.
GAS SUPP_
For Natural Gas, the minimum inlet gas supply pressure for the purpose of input adjustment is 5" column. The max- imum inlet gas supply pressure is 7" water column.
For L.R Gas, the minimum inlet gas supply pressure for the purpose of input adjustment is 11" water column. The maximum inlet gas supply pressure is 13" water column.
Gas pressures and input to the burners must not exceed
the rated input and pressure shown on the rating plate. On Natural Gas the manifold pressure should be 4 inches water column. The manifold pressure should be 11 inches water column for L.R Gas. See page 13 for operation above 2000 feet altitude. Orifice change may be required to suit gas supplied. Check with your local gas supplier.
ORIFICE SIZES
Furnace Technical Information, page 13, shows the cor-
rect orifice sizes for the different input ratings when using Natural or L.R Gas.
GAS PIPING
The gas supply line must be of adequate size to handle the BTU/HR requirements and length of the run for the unit being installed.
Determine the minimum pipe size from Fig. 10, page 11,
basing the length of the run from the gas meter or source to the unit.
All piping must comply with local codes and ordinances or with the National Fuel Gas Code (ANSI Z223.1 NFPA No. 54), whichever applies.
IN Canada: Follow
Refer to Fig. 8 for the general layout at the unit. It shows the basic fittings needed.
The following rules apply:
1.Use new, properly reamed pipe free from chips such as steel or black iron pipe and fittings or other approved by local codes.
2, Do not thread pipe too far. Valve distortion or malfunc- tion may result from excess pipe within control.
Apply moderate amount of good quality dope to pipe only, leaving 2 end threads bare. If L.R Gas installa-
tion, use compound resistant to action of liquefied petroleum gases.
3, Use ground joint unions.
4.Install a drip leg to trap dirt and moisture before it can enter the gas valve. Drip leg must be a minimum of 3 inches long.
5.Install a manual
|
|
| GAS SUPPLY PIPING |
DROP |
|
| |
] | I | PIPED | ;R0UN0 JOINT |
I | I | GAS | UNION |
J_ | SUPPLY |
| |
._;:_Hor ,ZON r AL i | 'l |
| ql, |
RISER
l,_ 176 2 mini | GAS |
MiNiMUMor_oP__" | SYUAANuAtSHUTAS | OFF | SUPPLY | |
_ |
|
|
| 3 ,_ 1/6 _ r.nd |
! | ( | SUPPLY | \ | |
I | ! |
|
| GAUGE |
I I
hi',se!,,
'I
I I
_/_ ALL BEttO5 iN M[TAL I.IC _ LJHING 514OULO B[ 5_,4OOTH
_" | _.AklTION | 511UT | OyF | [14[ | M_IN | _AS | SUppI.y | gEl'Oil[ | N[MOVING |
| Eft[) | 12,_p | ||
| ro | PN[VENT | GAS | FIt(IM | FILLING | Ttl[ | WORK | #.R_.A | TE.ST | _Ofl | GAS | L[AK |
| |
| AGE | WIt[N | IIN_TAI |
| LAIlON | IS | COMPI_ET[ |
|
|
|
|
|
|
|
PROPER PIPING PRACTICE
2 IMPERFECTCONTRO L USE MOOERATE AMOUNT OF DOP[ THREADS