Williams 2203612, 3003612, 2203611, 3003611, 1403611, 1403612 owner manual Start-UpProcedure

Models: 3003612 3003611 2203612 1403612 2203611 1403611

1 26
Download 26 pages 38.41 Kb
Page 14
Image 14
Start-Up Procedure

Start-Up Procedure

Start the furnace using the procedures in section CHECK THE GAS INPUT (NATURAL GAS ONLY) Operating Your Furnace on pages 15 through 19.

WARNING

DANGER OF BODILY INJURY OR DEATH

LIQUEFIED PETROLEUM (L.E) GAS IS HEAVIER THAN AIR AND IT WILL SETTLE IN ANY LOW

AREA, INCLUDING OPEN DEPRESSIONS AND IT WILL REMAIN THERE UNLESS AREA IS VENTILATED.

NEVER ATTEMPT START-UP OF UNIT BEFORE THOROUGHLY VENTILATING AREA•

Check the furnace operation as outlined in the following instructions• If any sparking, odors or unusual noises are encountered, shut off electrical power immediately. Recheck for wiring errors, or obstructions in or near op- tional blower motor•

NOTICE:

During the initial firing of this unit some smoke and odor may occur• We recommend ventilating the area during this initial "break in period."

CHECK GASlNPUT AND PRESSURES

For furnace located at altitudes between sea level and 2000 feet, the measured input must not be greater than the input shown on the rating plate of the furnace. For elevations above 2000 feet, the measured input must not exceed the input of the rating plate reduced by 4 percent for each 1000 feet that the furnace is above sea level.

Gas supply pressure and manifold pressure with the

burners operating must also be as specified on the rating plate.

TYPE OF GAS MANIFOLD PRESSURE, IN. W.C.

Natural

4

L.R

11

WARNING

NATURAL GAS HEATING VALUE (BTU PER CUBIC

FOOT) CAN VARY SIGNIFICANTLY, THEREFORE, IT IS THE INSTALLER'S RESPONSIBILITY TO SEE

THAT BTU INPUT TO THE FURNACE IS ADJUSTED PROPERLY. FAILURE TO DO SO COULD CAUSE HEAT EXCHANGER FAILURE, ASPHYXIATION, FIRE OR EXPLOSION, RESULTING IN DAMAGE, BODILY INJURY OR DEATH. REFER TO THE NATURAL

FUEL GAS CODE (NFPA-54) TO BE SURE THE FUR- NACE IS BURNING FUEL AT THE PROPER RATE.

Underfiringcould cause inadequate heat, excessiveconden- sation or ignition problems. Overfiring could cause soot- ing flame impingement or overheating of heat exchanger•

Before starting natural gas input check, obtain heating value of gas (BTU per cubic foot) at standard conditions from your local supplier. This factor is used in "Check the Gas Input" section and procedure.

To measure the input using the gas meter, proceed as follows:

Step 1: Turn off gas supply to all other appliances except the furnace.

Step 2: With the furnace operating, time the smallest dial on the meter for one complete revolution. If this is a 2 cubic foot dial, divide the seconds by 2; if it is a 1 cubic foot dial, use the time in seconds as is. (3,600 = Sec. Per Hr.) This gives the

seconds per cubic foot of gas being delivered to

• the furnace.

Step 3: Assuming natural gas with a heating value of 1000 Btu per cubic foot and 34 seconds per cubic foot as determined by step (2), then:

Input: 1,000 X 3,600 + 34 = 106,000 Btu Per Hour

This measured input must not be greater than the input indicated on the rating plate of the furnace.

Step 4: Relight all other appliances turned off in step 1 above. Be sure all pilot burners are operating.

ADJUST PILOT BURNER

Rated input will be obtained on 2500 B'FUpropane at 11 inches manifold pressure with factory-sized orifices. If L.R Gas having a different heating value is supplied, orifices must be changed by a qualified installer before the fur- nace is operated•

NOTE: Pilot gas may need adjustment depending on inlet pressure, increase or decrease to obtain proper setting.

Pilot flame should surround 3/8 inch to 112inch of the ther-

mocouple tip. To adjust, if needed, remove pilot adjustment cap (do not lose gasket).

CHECK THE MANIFOLD GAS PRESSURE

A tapped opening is provided in the gas valve to facilitate measuring the manifold gas pressure. A "U Tube"

manometer having a scale range from 0 to 12 inches of water should be used for this measurement. The manifold

pressure must be measured with the burner and pilot operating. Any major changes in the flow must be made by changing the size of the burner orifice. Check with local gas company for proper orifice size.

m14m

1, Remove screw cover over pilot adjusting screw.

2.Insert small screwdriver. Adjust flame as needed. Turn screw counterclockwise (I¢-_) to increase flame,

clockwise (_) to decrease.

3.Turn thermostat to highest setting. Main burners should light quickly and smoothly. Turn thermostat to lowest setting. Main burners should go out. Pilot should re- main lighted.

4.Replace screw cover over pilot adjusting screw.

Page 14
Image 14
Williams 2203612, 3003612, 2203611, 3003611, 1403611, 1403612 owner manual Start-UpProcedure