Configuring an M1 CPU with Modsoft

Setting the Time, Continued

Procedure

Follow the steps in the table below to set the register values for the time-of-day

 

clock:

 

 

 

 

 

 

 

Step

Action

 

 

 

 

 

1

Set the correct date and time in registers 4x + 1 through 4x + 7.

 

 

Example: To set the clock for Thursday, April 9, 1998 at 4:17:00, set the following

 

 

values in the registers:

 

 

4x + 1 5

 

 

4x + 2 4

 

 

4x + 3 9

 

 

4x + 4 98

 

 

4x + 5

4

 

 

l4x + 6

17

 

 

4x + 7

00

 

 

 

 

2

Load the value 8000H in register 4x to write the data to the clock.

 

 

 

 

 

 

 

 

230

870 USE 101 10 V.2

Page 230
Image 230
Schneider Electric Processor Adapter manual Procedure, Clock