Saving to Flash in Modsoft
870 USE 101 10 V.2 305
Saving to Flash
Conditions for
Saving to Flash In order to save the application program and state RAM values to Flash:
lThe Modsoft panel must be Online
lThe PLC must be stopped (not solving logic)
Save-to-Flash
Procedure Follow the steps below to save to Flash.
Continued on next page
Step Action
1With the PLC online, go to the Ladder diagram editor or the Segment Status
Display.
2From the PlcOps pull-down on the top menu, select Save to Flash.
Result: If the PLC is stopped when you select Save to Flash, the following screen
appears:
3Answer the first two questions to specify the way you want the PLC to restart after a
power-down.