Using the Modbus Ports
Two-Wire Cabling Schemes for Modbus RS485 Networks
Introduction | |||
|
| slave communications. Masters may be located anywhere in the network. | |
|
| CAUTION |
|
|
| POTENTIAL FOR MULTIMASTER CONFLICTS |
|
|
| Configure a multimaster network carefully to avoid masters issuing simultaneous or | |
|
| conflicting commands to the same slave module. |
|
|
| Failure to observe this precaution can result in injury or equipment damage. | |
Length |
|
| |
The maximum length of cable from one end of network to other is 2000 ft. (609 m). | |||
Number of |
|
| |
The maximum number of devices in a network is 64 if all are Momentum devices. | |||
Devices | Otherwise, the maximum is 32. |
| |
Termination |
|
| |
One end of the cable run must be terminated with a terminating resistor (color code | |||
|
| is red). |
|
|
| The other end of the cable must be terminated with a terminating shunt, which | |
|
| connects the transmit pair to the receiver pair (color code is blue). | |
|
|
|
|
|
| Description | Part Number |
|
|
|
|
|
| Modbus Plus or Modbus RS485 Terminating RJ45 Resistor Plugs | 170 XTS 021 00 |
|
| (pack of 2) |
|
|
|
|
|
|
| Modbus RS485 Terminating RJ45 Shunt Plugs | 170 XTS 042 00 |
|
|
|
|
Continued on next page