Using the Ethernet Port

 

 

 

 

 

Cabling Schemes

 

 

 

Introduction

 

 

 

 

In a standard Ethernet cabling scheme, each device connects via a cable to a port

 

on a central Ethernet hub.

 

 

Length

 

 

 

 

The maximum length of cable between devices depends on the type of hub used,

 

as shown in the following table:

 

 

 

 

 

 

 

 

Type of Hub

Max. Cable from

Max. Hubs Between

Max. Cable Between Most

 

 

Device to Hub

Any Two Nodes

Distant Nodes on Network

 

 

 

 

 

 

Traditional

100 m

4

500 m

 

(Non-switching)

 

 

 

 

 

 

 

 

 

Switches

100 m

Unlimited

Unlimited

 

 

 

 

 

Note: 10/100 hubs/switches can be used. This will allow 100 Base T networks to use the M1E.

Cabling with The following illustration shows the maximum number of hubs and the maximum Traditional Hubs cable length between devices when using traditional (non-switching) hubs:

Cabling with

Traditional Hubs

500m (1630 ft) Maximum Cable Length

Within the Same Collision Domain

M1E

M1E

HubHub

I/O Device

I/O Device

I/O Device

I/O Device

 

 

 

 

 

 

 

 

870 USE 101 10 V..2

147