Using the Modbus Ports

Four-Wire Cabling Schemes for Modbus RS485 Networks

Introduction

Four-wire cabling schemes may be used for single master/slave communications.

 

Only one master is allowed. The master may be located anywhere in the network.

Length

 

 

The maximum length of cable from one end of network to other is 2000 ft. (609 m).

Number of

 

 

The maximum number of devices in a network is 64 if all are Momentum devices.

Devices

Otherwise, the maximum is 32.

 

Termination

 

 

You must terminate both ends of the cable run with special terminating resistors.

 

 

 

 

Description

Part Number

 

 

 

 

Modbus Plus or Modbus RS485 Terminating RJ45 Resistor Plugs

170 XTS 021 00

 

(pack of 2).

 

 

Color code - red

 

Master Cable

 

 

 

 

The master of this master/slave cabling scheme must be connected on at least one

 

side to a master cable, a special cable that crosses the transmit and receive lines.

 

The other side may be connected to a master cable, or, if the master is at one end

 

of the cable run, a terminating resistor.

 

 

 

 

 

Description

Part Number

 

 

 

 

Modbus RS485 (RJ45/RJ45) Master Communication Cable

170 MCI 041 10

 

 

 

 

Modbus Plus or Modbus RS485 Terminating RJ45 Resistor Plugs

170 XTS 021 00

 

(pack of 2).

 

 

Color code - blue

 

 

 

 

 

 

 

 

 

Continued on next page