Configuring a Modbus Plus Network in Concept with Peer Cop

Other Default Settings in the Peer Cop Dialog Box

Overview

This section describes the default settings for Health Timeout and Last Value.

Diagram

 

The first time you access the Peer Cop dialog box, the following screen appears:

Health Timeout The default Timeout is 500 ms.

Timeout is the maximum interval that Modbus Plus on a Peer-Copped device will remain healthy without communication activity. If this interval is exceeded, the device will clear its network health bit and will no longer try to communicate via Modbus Plus.

The timeout interval must be in the range 20...2000 ms, and it must be specified as an increment of 20 ms.

Continued on next page

374

870 USE 101 10 V.2

Page 374
Image 374
Schneider Electric Processor Adapter manual Other Default Settings in the Peer Cop Dialog Box