Run LED Flash Patterns and Error

Codes

Run L7ED Flash The following table lists the flash pattern of the Run LED on the Momentum Pattern and Error Processor Adapters. It also lists the associated codes (in hex format).

Codes

Number of Blinks

Code (hex)

Error

 

 

 

Continuous

0000

Requested Kernel mode

 

 

 

2

080B

ram error during sizing

 

 

 

 

080C

run output active failed

 

 

 

 

082E

MB command handler stack error

 

 

 

 

0835

Main loop broken

 

 

 

 

0836

Power down / Power holdup

 

 

 

 

0837

Power down reset absent

 

 

 

3

072B

master config write bad

 

 

 

Continued on next page