Configuring an M1 CPU with Modsoft
Changing the Baud Rate
Overview | Each port can be configured for a baud in the range 50...19,200. Sixteen valid |
| bauds are |
Note: If you use a baud rate lower than 4800, you should adjust the default delay parameter. See Changing the Delay on page 240.
Procedure | To change the baud parameter, perform the steps in the following table. |
|
|
| Step Action |
1Place the cursor on the current Baud entry for the Modbus port you want to enter. Push <Enter>.
Result: A popup window appears in the top left corner of the screen displaying 16 baud values:
2
Use an arrow key to toggle the cursor onto the desired Baud selection in the popup window, then push <Enter>.
Result: The Port editor screen is updated with the Baud number you have specified, and the cursor moves to the
238 | 870 USE 101 10 V.2 |