Using the Modbus Plus Ports
Cluster Mode Cabling Schemes, Continued
Termination | You must terminate both ends of the network with special terminating resistors. | |
|
|
|
| Description | Part Number |
|
|
|
| Modbus Plus or Modbus RS485 Terminating RJ45 Resistor Plugs | 170 XTS 021 00 |
| (pack of 2) |
|
|
|
|
|
|
|
Cable Between
Nodes in a
Cluster
Cable Between Clusters
Drop Cables
The minimum length of cable between nodes in a cluster is 10 in (.25 m).
Description | Part Number |
|
|
Modbus Plus / Modbus RS485 Short Interconnect Cable | 170 MCI 020 10 |
|
|
Modbus Plus or Modbus RS485 3 ft. Interconnect Cable | 170 MCI 020 36 |
|
|
|
|
The minimum length of cable between clusters is 10 ft. (3 m).
Description | Part Number |
|
|
Modbus Plus or Modbus RS485 10 ft. Interconnect Cable | 170 MCI 021 80 |
|
|
Modbus Plus or Modbus RS485 30 ft. Interconnect Cable | 170 MCI 020 80 |
|
|
|
|
Drop cables connecting a cluster to the trunk cable must be at least 10 ft. (3 m) long. A 10 ft. drop cable is available. A 30 ft. drop cable may be fabricated by removing one RJ45 connector from a 30 ft. interconnect cable. Connect the open end of the cable to a Modbus Plus tap, using the wiring illustrations on page 194.
Description | Part Number |
|
|
Modbus Plus 10 ft. Drop Cable | 170 MCI 021 20 |
|
|
Modbus Plus or Modbus RS485 30 ft. Interconnect Cable | 170 MCI 020 80 |
|
|
|
|
| Continued on next page |
188 | 870 USE 101 10 V.2 |