Overview of Momentum M1 Processor Adapters
171 CCC 960 20, Continued |
|
| |
Specifications, |
|
|
|
|
|
| |
Input and Output References |
| ||
Continued |
| ||
|
|
| |
| Registers | 26048 |
|
|
|
|
|
| Discretes | 8192 0x references |
|
|
| 8192 1x references |
|
|
|
|
|
| I/O Servicing |
|
|
|
|
|
|
| Local I/O | Services all the points on any host Momentum I/O base |
|
|
|
|
|
| Watchdog timeout | 335 ms |
|
|
|
|
|
| Logic solve time | See formula, following |
|
|
|
|
|
| Mechanical |
|
|
|
|
|
|
| Weight | 42.5 g (1.5 oz.) |
|
|
|
|
|
| Dimensions (HxDxW) | 25.9x61.02x125mm |
|
|
| (1.01 x 2.37 x 4.86 in) |
|
|
|
|
|
| Material (Enclosures/ | Lexan |
|
| bezels) |
|
|
|
|
|
|
| Operating Conditions |
|
|
|
|
|
|
| Temperature | 0 ... 60 degrees C |
|
|
|
|
|
| Humidity | 5 ... 95% (noncondensing) |
|
|
|
|
|
| Chemical interactions | Enclosures and bezels are made of Lexan, |
|
|
| a polycarbonate that can be damaged by strong |
|
|
| alkaline solutions |
|
|
|
|
|
| Altitude, full operation | 2000m (6500ft) |
|
|
|
|
|
| Vibration | 10 ... 57Hz @ 0.075mm displacement amplitude |
|
|
| 57...150Hz @ 1g |
|
|
| Ref. IEC |
|
|
|
|
|
| Shock |
| |
|
| Ref. IEC |
|
|
|
|
|
| RFI Susceptibility/ | Meets CE mark requirements for open equipment. |
|
| immunity | Open equipment should be installed in an industry- |
|
|
| standard enclosure, with access restricted to qualified |
|
|
| service personnel. |
|
|
|
|
|
|
|
|
|
|
| Continued on next page | |
870 USE 101 10 V.2 | 49 |