Option Adapters

Front Panel Components, Continued

LED Indicator This Option Adapter has one LED indicator, the MB+ ACT indicator. This indicator flashes the following patterns, based on the status of the Modbus Plus node:

Pattern

Meaning

 

 

6 flashes/s

This is the normal operating state for the node. It is receiving

 

and passing the network token. All nodes on a healthy

 

network flash this pattern.

 

 

1 flash/s

The node is offline just after power-up or after exiting the

 

6 flashes/s mode. In this state, the node monitors the

 

network and builds a table of active nodes. After being in

 

this state for 5s, the node attempts to go to its normal

 

operating state, indicated by 6 flashes/s.

 

 

2 flashes, then OFF for 2s

The node detects the token being passed among the other

 

nodes, but never receives the token. Check the network for

 

an open circuit or defective termination.

 

 

3 flashes, then OFF for 1.7s

The node is not detecting any tokens being passed among

 

the other nodes. It periodically claims the token but cannot

 

find another node to which to pass it. Check the network for

 

an open circuit or defective termination.

 

 

4 flashes, then OFF for 1.4s

The node has detected a valid message from a node using a

 

network address identical to its own address. The node

 

remains in this state for as long as it continues to detect the

 

duplicate address. If the duplicate address is not detected

 

for 5s, the node changes to its 1 flash/s mode.

 

 

ON

Indicates an invalid node address.

 

 

OFF

Possible fault with Modbus Plus Option Adapter.

 

 

Continued on next page

870 USE 101 10 V.2

75

Page 75
Image 75
Schneider Electric Processor Adapter manual Pattern Meaning