Configuring a Modbus Plus Network in Concept with Peer Cop
Specifying References for Input and Output Data
Overview | We will now set up the 171 CCS 760 00 Momentum M1 CPU at Modbus Plus | |
| address 2 to: | |
| λ send eight 4x registers of specific output to the supervisory computer at | |
| Modbus Plus address 1. | |
| λ receive five 4x registers of global input data from the ATRIUM supervisor. | |
| These registers are the first five registers in a | |
| outputs broadcast by the supervisory controller. | |
| Note: For this example, we will use the default values for Health Timeout (500 | |
|
| ms) and Last Value (Clear on timeout). |
Defining the |
|
|
The following table describes how to define the specific output, starting from the | ||
Specific Output | Peer Cop dialog box. | |
|
|
|
| Step | Action |
|
|
|
| 1 | Click on the Specific Output... button. |
|
| Result: The Specific Output dialog box appears. |
|
|
|
|
|
|