Overview of Momentum M1 Processor Adapters
171 CCC 980 20, Continued
Specifications,
Continued
Storage Conditions
Temperature | |
|
|
Humidity | 5 ... 95% (noncondensing) |
|
|
Safety Parameters |
|
|
|
Degree of protection | Unintentional access (UL 508 Type 1, NEMA250 Type 1, |
| IP20 conforming to IEC529) |
|
|
Ethernet is isolated from logic common 500 VDC | |
|
|
Ground continuity | 30 A test on the exposed metal connector |
|
|
Agency Approvals | lUL 508, CSA, CUL, CE |
| FM class1, div2 |
|
|
Scantime Formula for 984LL Exec
Example
The following formula applies to the M1E Processor Adapter with the 984LL exec.
Scan time = (0.25 msec/ethernet device + 0.002 msec/word) + 0.13 msec/K of logic + 0.40 msec + MBPlustime
Note:
Modbus Plus communications will slow the M1E. If there is no MB+ ring card then MBPlustime = 0.
If there is a MB+ ring card, then each scan will be extended 0.3 Msec even if there is no message.
Modbus Messages will add from 1 to 2 msec per scan, depending on the length of the message.
Note:
The formula above presumes that all MSTR blocks and all configured connections are set to go as fast as possible. In this case the M1E will attempt to exchange data with
leach device once per scan.
If several devices are configured to communicate on a timed basis that is substantially larger than the scan time calculated, then the communications to those devices will be spread out over several scans. See Example, below.
You have 50 ENT modules connected to a single M1E with a configured time of 50 Msec each, a total of 4k user logic and no MB+ card. The scan time for all modules configured as fast as possible would be 12.5 Msec + 0.52 Msec + 0.40 Msec =
13.42Msec. However, since the M1E will only communicate to 1/4 of the modules
(12.5 Msec/50 Msec = 1/4) on any given scan, the corrected average scan time would be 1/4 x (12.5) + 0.52 + 0.40 ≅ 4.1 Msec.
870 USE 101 10 V.2 | 59 |