
Using the Modbus Plus Ports
Modbus Plus Addresses
Introduction | Modbus Plus devices function as peers on a logical ring. Each device accesses the |
| network by acquiring a token frame that is passed in a rotating address sequence. |
| Each device on a Modbus Plus network needs a unique address in the range |
| 1...64. The device address determines the logical order in which the network token |
| will be passed from device to device. |
|
|
CAUTION
COMMUNICATION ERRORS MAY RESULT
Do not install a Modbus Plus Option Adapter before you have set its Modbus Plus address for your application. See your network administrator to get the Modbus Plus node address for this module.
Failure to observe this precaution can result in injury or equipment damage.
Address | The assignment of addresses does not have to map to the physical layout of the |
Sequence | |
| understand because the network's token rotation is defined by device addresses- |
| e.g., device 2 will pass the token to device 3, device 3 to device 4, etc. |
|
|
Illegal Addresses If you set the node address to 00 or to a value greater than 64:
λThe COM LED will go ON steadily to indicate an illegal address assignment.
λThe Run LED will flash 4 times.
λThe Processor Adapter will not run until you set a valid, unused address on the Option Adapter and cycle power.
Continued on next page
198 | 870 USE 101 10 V.2 |