Configuring a Modbus Plus Network in Concept with Peer Cop
870 USE 101 10 V.2 393
Defining the References for the Next Node
Overview We now want to attach the Concept 2.2 programming pa nel to the 17 1 CCS 7 60 00
Momentum M1 CPU at Modbus Plus address 3 and create a similar Peer Cop for
this device to communicate with the supervisory PLC at Modbus Plus address 1. In
this case, we want the M1:
lto send 16 words of specific output to the supervisor.
lto receive the last seven words of global input from the superv isor. (Remember
that the supervisor will be transmitting a total of 10 contiguous words of global
data over the network.)
Continued on next page