Configuring a Modbus Plus Network in Concept with Peer Cop
Defining the References for the Next Node
Overview | We now want to attach the Concept 2.2 programming panel to the 171 CCS 760 00 |
| Momentum M1 CPU at Modbus Plus address 3 and create a similar Peer Cop for |
| this device to communicate with the supervisory PLC at Modbus Plus address 1. In |
| this case, we want the M1: |
| λ to send 16 words of specific output to the supervisor. |
| λ to receive the last seven words of global input from the supervisor. (Remember |
| that the supervisor will be transmitting a total of 10 contiguous words of global |
| data over the network.) |
|
|
| Continued on next page |
870 USE 101 10 V.2 | 393 |