Configuring a Modbus Plus Network in Concept with Peer Cop

Defining References for the Supervisory PLC, Continued

Defining the

This supervisory CPU sends out 10 words of global output, parts of which are

Global Outputs

received by each of the M1 CPUs.

 

 

 

 

Step

Action

 

 

 

 

1

Click on the Global Output... button.

 

 

Result: The Global Output dialog box appears.

2

3

In the Source Ref. column, type the value 400033, the first register which will be sent.

In the Length column, type the value 10, the number of registers that will be sent.

4

Click <OK>.

870 USE 101 10 V.2

397

Page 397
Image 397
Schneider Electric Processor Adapter manual Global Outputs, Received by each of the M1 CPUs