Configuring an M1 CPU with Modsoft
Changing the Protocol on Modbus Port 2
Overview | If your Momentum M1 CPU is using the Modbus Port 2 provided by the 172 JNN |
| |
|
| 210 32 Option Adapter, you can specify whether it will use the RS232 or RS485 |
|
|
| protocol. The |
|
|
| If you are using the Modbus Port 2 provided on the 171 CCS 780 00 or |
|
|
| 171 CCC 780 10 Processor Adapter, the port is hardwired as a dedicated RS485 |
|
|
| protocol. However, you must change the default setting on the Port editor screen |
|
|
| from RS232 to RS485, or the port will not function. |
|
Procedure |
|
| |
From the Port editor screen, perform the steps in the following table to change the |
| ||
|
| Protocol on Modbus Port 2. |
|
|
|
|
|
|
| Step Action |
|
1Place the cursor on the current Protocol entry for Modbus port 2. Push <Enter>.
Result: A popup window appears in the top left corner of the screen displaying the two protocol options:
2
Use an arrow key to toggle the cursor onto the desired protocol selection in the popup window, then push <Enter>.
Result: The Port editor screen is updated with the protocol you have specified.
870 USE 101 10 V.2 | 241 |