Using the Modbus Plus Ports
Standard Cabling Schemes
Introduction | In a standard Modbus Plus cabling scheme, each peer device connects via a drop | |
| cable to a tap along a trunk cable. |
|
Length |
|
|
The maximum length of cable from one end of the network to the other is 1500 ft. | ||
| (450 m) if no repeaters are used. |
|
| You can use up to three Modicon RR85 Repeaters to extend the cable to up to | |
| 6000 ft. (1800 m). Each repeater allows you to extend the cable 1500 ft. (450 m). | |
|
|
|
| Description | Part Number |
|
|
|
| Modicon RR85 Repeater | |
Distance |
|
|
|
| |
Nodes must be separated by at least 10 ft. of cable. This requirement is more than | ||
Between Nodes | satisfied by standard drop cables: |
|
|
|
|
| Description | Part Number |
| Modbus Plus Drop Cable, 2.4 m / 8 ft. | 990 NAD 211 10 |
| Modbus Plus Drop Cable 6 m / 20 ft. | 990 NAD 211 30 |
Number of |
|
|
|
| |
The maximum number of devices in a network is 64: |
| |
Devices | λ If you use only Momentum products, you may use up to 64 devices on one | |
| ||
| cable section without a repeater. |
|
| λ If you use a mixture of devices, you may use up to 32 devices on one cable | |
| section. You must use a repeater to connect to another cable section. You may | |
| use up to three repeaters and four cable sections in all. |
|
Termination |
|
|
You must terminate both ends of the network. If your network consists of two or | ||
| more sections separated by a repeater, each section must be terminated at both | |
| ends. |
|