Using Peer Cop with Modsoft
Specifying References for Input and Output Data
Overview | We will now set up the 171 CCS 760 00 Momentum M1 CPU at Modbus Plus |
| address 2. This device will: |
| λ send eight 4x registers of specific output to the supervisory computer at |
| Modbus Plus address 1. |
| λ receive five 4x registers of global input from the supervisory computer. These |
| registers are the first five registers in a |
| supervisor. |
|
|
Defining the | The following table describes how to define the specific output in Peer Cop. | |
Specific Output |
|
|
| Step | Action |
1Move the cursor to the REFERENCE column of the SPECIFIC OUTPUT field with the cursor arrow keys.
2In the REFERENCE column of the SPECIFIC OUTPUT field, type the value 400016. Push <Enter>.
Result: The cursor moves into the LEN column of the SPECIFIC OUTPUT field.
Continued on next page
870 USE 101 10 V.2 | 287 |