Using Peer Cop with Modsoft

Specifying References for Input and Output Data, Continued

Defining the

Now the M1 needs to be Peer Copped to receive five words of global data from the

Global Inputs

supervisory PLC at Modbus Plus address 1. Follow the steps in the table below to

 

specify the global input references.

Step Action

1In the REFERENCE column on the first line of the GLOBAL INPUT field, type the value 400001, the first register in which the CPU will store data. Push <Enter>.

Result: The cursor moves into the LEN column of the GLOBAL INPUT field.

Continued on next page